B. Assemble Vent Sections (SLP Pipe Only)

To attach the fi rst vent component to the starting collars
of the appliance:

• Lock the vent components into place by sliding the pipe

section onto the collar.

• Align the seam of the pipe and seam of collar to allow

engagement. Rotate the vent component to lock into
place. Use this procedure for all vent components. See
Figure 8.5.

• Slide the gasket over the fi rst vent section and place it

fl ush to the appliance. This will prevent cold air infi ltration.
High temperature caulk may be used to hold the part in
place.

• Continue adding vent components, locking each

succeeding component into place.

• Ensure that each succeeding vent component is securely

fi tted and locked into the preceding component.

Commercial, Multi-family (Multi-level exceeding two sto-
ries), or High-Rise Applications

For Installation into a commercial, multi-family (multi-level
exceeding two stories) or high-rise applications: All outer
pipe joints must be sealed with high temperature silicone,
including the slip section that connects directly to the hori-
zontal termination cap.

• Apply a bead of silicone sealant inside the female outer

pipe joint prior to joining sections. See Figure 8.1.

• Only outer pipes need to be sealed. All unit collar, pipe,

slip section, elbow and cap outer fl ues shall be sealed
in this manner, unless otherwise stated.

Figure 8.5 Adding Venting Components

WARNING! Risk of Fire or Explosion! DO NOT break
silicone seals on slip sections. Use care when remov-
ing termination cap from slip pipe. If slip section seals
are broken during removal of the termination cap, vent
may leak.

Note: Align seams to engage pipe,
then rotate counterclockwise to lock

C. Assemble Slip Sections

• Slide the inner fl ue of the slip section into the inner fl ue

of the pipe section and the outer fl ue of the slip section
over the outer fl ue of the pipe section. See Figure 8.6.

• Slide together to the desired length.

Figure 8.6 Slip Section Pilot Holes

Figure 8.7 Screws into Slip Section

Pilot hole

Pilot hole

NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a high temperature silicone sealant.

Apply a bead of silicone sealant inside the female outer

pipe joint prior to joining sections.

Only outer pipes are sealed, sealing the inner fl ue is not

required.

All unit collar, pipe, slip section, elbow and cap outer

fl ues shall be sealed.

• Continue adding pipe as necessary following instructions

in “Assembling Pipe Sections.”

NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.

• Maintain a 1-1/2 in. (38 mm) overlap between the slip

section and the pipe section.

• Secure the pipe and slip section with two screws no

longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 8.7.