Two elbows – Heat & Glo Fireplace 6000G-IPI User Manual

Page 16

Advertising
background image

Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08

16

Figure 5.11

Two Elbows

Figure 5.10

4. Center the Flue Restrictor on vent and secure in place

by using two self-tapping screws (see Figure 5.10).

5. Reinstall the Exhaust Shield.

3. Match the amount of vertical you have in the sys-

tem with the chart to fi nd the appropriate position
to set the Flue Restrictor (see Figure 5.9 ).

Figure 5.9

1 2 3 4 5

S E TTIN G S

1 2 3 4 5

Vertical

TOP VENT

REAR VENT

NG

LP

NG

LP

4 ft.

1-1

No

Restrictor

No

Restrictor

No

Restrictor

8 ft.

2-2

1-2

1-1

No

Restrictor

15 ft.

3-3

3-2

2-2

1-2

20 ft.

3-4

3-3

3-3

2-3

25 ft.

3-4

3-3

3-3

2-3

30 ft.

4-4

3-4

3-4

3-3

35 ft.

4-4

3-4

3-4

3-3

40 ft.

5-4

4-4

4-4

3-4

Note: If the DVP-2SL adapter and SLP pipe is used, you

MUST subtract one number from the table above.

Example: Top vent 40 ft vertical with DVP pipe = 5-4

Top vent 40 ft vertical with SLP pipe = 4-3

V

1

H

1

Maximum

V

2

V

1

+ V

2

Min.

Elbow only

2 ft.

610 mm

*

*

*

6 in.

152 mm

6 ft.

1.8 m

*

*

*

2 ft.

610 mm

11 ft.

3.4 m

*

*

*

3 ft.

914 mm

16 ft.

4.9 m

*

*

*

4 ft.

1.2 m

20 ft

6.1 m

*

*

*

V

1

+ V

2

+ H

1

= 50 ft (15.2 m) Maximum

*No specifi c restrictions on this value EXCEPT

V

1

+ V

2

+ H

1

cannot exceed 50 ft (15.2 m)