Rear vent - vertical termination one elbow, Two elbows – Heat & Glo Fireplace 6000G-IPI User Manual

Page 20

Advertising
background image

Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08

20

IN S TA LL E D

H O R IZ O N TA L LY

4. Rear Vent - Vertical Termination

One Elbow

Figure 5.17

Two Elbows

Figure 5.18

V

1

Minimum

H

1

Maximum

6 in.

152 mm

2 ft.

610 mm

1 ft.

305 mm

3 ft.

914 mm

2 ft.

610 mm

5 ft.

1.5 m

3 ft.

914 mm

7 ft.

2.1 m

4 ft.

1.2 m

8 ft

2.4 m

5 ft.

1.5 m

8 ft

2.4 m

V

1

+ H

1

= 40 ft (12.2 m) Maximum

H

1

= 8 ft (2.4 m) Maximum

H

1

+ H

2

Maximum

V

1

Minimum

Back to Back 90° Elbows

3 ft.

914 mm

2 ft

610 mm

6 ft.

1.8 m

4 ft

1.2 m

9 ft.

2.7 m

6 ft.

1.8 m

12 ft.

3.7 m

8 ft.

2.4 m

15 ft.

4.6 m

V

1

+ H

1

= 40 ft (12.2 m) Maximum

H

1

+ H

2

= 8 ft (2.4 m) Maximum