Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08

15

2. Top Vent - Vertical Termination

No Elbow

Note: If installing a vertical vent/
termination off the top of the appli-
ance, the optional vertical termina-
tion baffl e should be used.

V

1

= 40 ft. Max. (12.4 m)

V

1

= 3 ft. Min. (914 mm)

Flue Restrictor Instructions

1. Remove Exhaust Shield using a 1/4 inch nut driver by

removing the four screws securing it in place (see Figure
5.7).

Figure 5.8 Flue Restrictor

2. Break the Flue Restrictor into two pieces. Do this by

bending the part back and forth until it breaks (see
Figure 5.8).

Figure 5.6

Figure 5.7

E X H A U S T

S H IE LD

FLU E

R E S TR IC TO R

B R E A K

H E R E