B) service menu chart – Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual

Page 22

Advertising
background image

22

Service
Menu

Item and Details

Setting Range

Factory Default

Cabinet

Rail

Cabinet

Rail

F0

Defrost Interval
• The cabinet uses a time initiated

heated defrost.

• The change in the defrost

interval setting will take effect
immediately. The next defrost
will take place after the newly
set time interval has elapsed.

• Initiating a manual defrost on the

cabinet will restart the defrost
timer.

1 to 12 hours in

1 hour increments.

N/A

6

N/A

F1

Defrost Termination Temperature
Do not adjust. For
recommendations, contact
Hoshizaki Technical Support.

41 to 68°F

(5 to 20°C)

in 1 degree

increments

N/A

49°F (9.4°C)

N/A

F2

Setpoint Temperature Differential
Use "SET" button to scroll through
all 4 settings.
• You cannot set both + and ‑ to

0.0.

• Negative value indicated by LED

to left of number.

Both the + and - values can be
adjusted between 0 to 6.3°F in
increments of .9°F
(0 to 3.5°C in increments of .5°C)
(decimal not displayed)

Comp on

0°F (0°C)

at setpoint

Comp off

-3.6°F (-2°C)

below setpoint

Comp on

0°F (0°C)

at setpoint

Comp off

-3.6°F (-2°C)

below setpoint

F3

High Temperature Alarm Delay
Time: See "III.A. Alarm Signals."

0 to 3 hours in 1 hour increments

2

F4

Low Temperature Alarm Delay
Time: See "III.A. Alarm Signals."

0 or 1 hour

1

F5

Temperature Display

Fahrenheit or Celsius

°F

F6

Alarm History: maximum 8 alarms.

No reset for alarm history
available.

Alarms displayed newest to oldest.
When "‑‑" appears, you have
reached the end of the alarm
history.

N/A

F7

Compressor Run Time (%):
Displays compressor run time
percentage between the 2 most
recent defrosts.

N/A

N/A

F8

Not Used

N/A

N/A

F9

Rail Cooling Switch:
"LOW" Rail Fan Adjustment (rail
section only)

0=rail fans on continuously (same
as "NORMAL" position)
1=rail fans on 15 sec.
rail fans off 90 sec.
2=rail fans on 1 sec.
rail fans off 90 sec.

N/A

2

FA

Do not

adjust

High Condenser Temperature
Alarm Setting (clogged filter):
For recommendations, contact
Hoshizaki Technical Support.

Adjustable between 140 to 167°F
(60 to 75°C).

140°F (60°C)

(1 not displayed)

Fb

Audible Control

N/A

N/A

b) Service Menu Chart