Cabinet cooling – Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual

Page 34

Advertising
background image

34

Problem

Possible Cause

Remedy

[3] Compressor will

not start or
stops operating.
(continued)

f) Voltage

1. Too low.

1. Call electrician.

2. Too high.

2. Call electrician.

g) High Pressure Switch

1. Restricted air flow to

condenser.

1. Move unit or increase

ventilation.

2. Condenser air filter

and/or condenser
clogged.

2. Clean.

3. Bad contacts.

3. Check continuity and

replace.

4. Condenser fan motor.

4. See [2] a) and b).

g) High Pressure Switch

(continued)

5. Refrigerant line or

component plugged or
restricted.

5. Recover, remove

restriction, replace drier,
evacuate, and recharge.

6. Refrigerant overcharge. 6. Recover, evacuate, and

recharge.

7. Non-condensibles in

system.

7. Recover, replace drier,

evacuate, and recharge.

h) Thermistors (cabinet

and rail)

1. Defective.

1. See "II.E. Thermistor

Check."

i) Compressor Overload 1. Defective. (open

contacts)

1. Replace.

j) Compressor

1. Open windings.

1. Check for continuity and

replace.

2. Locked rotor.

2. Replace.

k) Control Board

1. In alarm or defective.

1. See "III.A. Alarm Signals"

or replace

2. Cabinet Cooling

Problem

Possible Cause

Remedy

[1] Cabinet

temperature too
high.

a) Warm Food

1. Warm food recently

placed in cabinet area.

1. Pre-cool food or allow time

for unit to return to setpoint
temperature.

b) Doors/Drawers

1. Left open, opened too

often.

1. Close.

2. Not sealing, opened

frequently, or open for
long intervals.

2. Check for sealing, check for

door open at time of warm
cabinet temperature.

c) Outside Heat Source

1. Too close to unit.

1. Separate unit from heat

source.

d) Air Flow

1. Blockage inside

cabinet.

1. Remove blockage by

removing or redistributing
food product.

e) Cabinet Thermistor

1. Defective.

1. See "II.E. Thermistor

Check."

f) Setpoint and/or

Temperature
Correction Factor

1. Incorrect.

1. Correct setting(s).

See "II.D.4.c) Temperature
Setpoint" or
"II.D.4.f) Temperature
Correction Factor" for
defaults.