High temperature alarm (e1) – Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual

Page 27

Advertising
background image

27

1. High Temperature Alarm (E1)

If the cabinet or rail temperature exceeds the setpoint temperature by 18°F (10°C) or
more for more than x hours, "E1" is displayed. The default value of x is "2" (2 hours).
The value of x can be changed under "F3" on the service menu. (0=No delay; 1=1; 2=2;
3=3 hours)

Note:

• After the machine has been turned off and then turned back on, the high

temperature alarm feature is not active until the area temperature reaches the
lower setpoint temperature differential.

• The high temperature alarm feature operates even during defrost.

Reset Options
The alarm will automatically reset once the area temperature reaches the lower setpoint
temperature differential.

Possible Causes (for further details, see "III.B. Service Chart")
• Doors or drawers are opened frequently or are not completely closed.
• Trouble with the compressor or a refrigerant leak.
• Trouble with the cabinet or rail thermistor.
• Liquid line valve closed.

E1 Alarm Timer
over 2 hours

E1 Alarm Timer Reset

E1 Alarm
Timer under
2 hours

Power On

E1 Alarm Temperature 18°F
(10°C) above setpoint temp.

Setpoint Temperature and
Upper Setpoint Differential 0°F (0°C)

Lower Setpoint
Temperature Differential
3.6°F (2°C)

E1
Alarm
Reset

Temperature Display

E1
Blinking

E1 Alarm
Available

E1 Alarm

E1 Alarm not Available until
Lower Setpoint is Achieved