Cabinet defrost – Hoshizaki REFRIGERATED PREP TABLE WITH RAISED RAIL 73168 User Manual

Page 37

Advertising
background image

37

4. Cabinet Defrost

Problem

Possible Cause

Remedy

[1] Cabinet fan motors

on.

a) Cabinet Fan Relay

1. Bad contacts (closed). 1. Check for continuity and

replace.

b) Control Board

1. Defective.

1. Replace.

[2] Evaporator does

not defrost
completely.

a) Defrost Thermistor

1. Defective.

1. See "II.E. Thermistor

Check."

b) Defrost

1. Not enough defrosts

occurring per day.
Operation in humid
conditions.

1. Factory default is once

every 6 hours. See "II.D.5.
Service Menu."

c) Defrost Heater

1. Defective.

1. Replace heater.

d) Defrost Thermostat

1. Defective, turning off

heaters prematurely,
or fused open.

1. Replace defrost thermostat.

e) Cabinet Liquid Line

Valve

1. Does not close.

1. Check and replace.

[3] Defrost cycle too

long. (E3 Defrost
Alarm)

a) Defrost

1. Not enough defrosts

occurring per day.
Operation in humid
conditions.

1. Factory default is once

every 6 hours. See "II.D.5
Service Menu."

b) Defrost Thermistor

1. Defective.

1. Replace.

c) Defrost Heater

1. Defective.

1. Replace heater.

d) Defrost Thermostat

1. Defective, turning off

heaters prematurely,
or fused open.

1. Replace defrost thermostat.

e) Control Board

1. Defective.

1. Replace.