NATIONAL POWER DEVIATION STANDARDS

AUSTRALIA / NEW ZEALAND

COMPONENTS COMPLY WITH THE RELEVANT PORTIONS OF IEC 60950 OR THE
APPLICABLE COMPONENT STANDARD OR THE RELEVANT AUSTRALIAN / NEW ZEALAND
STANDARD.

AC POWER DISTRIBUTION SYSTEMS CLASSIFIED AS TT OR IT ARE NOT ALLOWED
INTENDED FOR USE ON A TN SYSTEM.

--------------------------------------------------------------------

Rated

Nominal

Current of

cross-sectional

Equipment

area

(A)

(mm²)

--------------------------------------------------------------------
0.2

<=

3 0.5*

3

<=

7.5 0.75

7.5

<=

10 (0.75) 1.00

10

<=

16 (1,0) 1.5

16

<=

25 2.5

25

<=

32 4

32

<=

40 6

40

<=

63 10

63

<=

80 16

80

<=

100 25

100

<=

125 35

125

<=

160 50

160

<=

190 70

190

<=

230 95

DENMARK

CERTAIN TYPES OF CLASS I APPLIANCES MAY BE PROVIDED WITH PLUG NOT
ESTABLISHING EARTHING CONTINUITY WHEN INSERTED INTO DANISH SOCKET-OUTLETS.

"VIGTIGT !

LEDEREN MED GRØN/GUL ISOLATION MÅ KUN

TILSLUTTES EN KLEMME MÆRKET

(IEC 417, NO. 5019) ELLER (IEC 417, NO. 5017)

FOR TILSLUTNING AF DE ØVRIGE LEDERE, SE MEDFØLGENDE

INSTALLATIONSVEJLEDNING

SUPPLY CORD OF SINGLE-PHASE EQUIPMENT HAVING A RATED CURRENT NOT
EXCEEDING 13 A SHALL BE PROVIDED WITH A PLUG ACCORDING TO THE HEAVY
CURRENT REGULATIONS, SECTION 107-2-D1. CLASS I EQUIPMENT PROVIDED WITH
SOCKET-OUTLETS WITH EARTH CONTACT OR WHICH ARE INTENDED TO BE USED IN
LOCATIONS WHERE PROTECTION AGAINST INDIRECT CONTACT IS REQUIRED ACCORDING
TO THE WIRING RULES SHALL BE PROVIDED WITH A PLUG IN ACCORDANCE WITH
STANDARD SHEET DK 2-1A OR DK 2-5A. IF POLY-PHASE EQUIPMENT AND SINGLE-PHASE