Maintenance – Harman Stove Company PB 105 User Manual

Page 34

Advertising
background image

34

3-90-07205R19_05/13

Maintenance

The boiler

MUST be OFF and COOl before you should

attempt to clean the combustion blower.
The wire to the combustion blower doesn’t need to be

disconnected during the cleaning process.
Loosen the three (3) thumb screws about 4 turns each.

See Fig. 23. Hold the motor head with one hand and the

blower plate handle with the other hand. Pull outward

on the plate handle until the complete unit comes loose.

Now rotate the plate counter-clockwise about 1/8 turn.

This will allow the complete assembly to be removed

from the blower chamber.
Clean the blower fan blades and the blower plate

sealing overlap. See Fig. 24.
NOTE: Be careful not to bend the fan blades,

this will throw the fan blade out of balance or it

may rub the inner chamber, which may affect the

performance of the boiler. Any horizontal and

vertical flue pipe directly above the unit should be

cleaned at this time
NOTE: The horizontal flue pipe directly above the

boiler is the first place fly ash will settle, due to

the slowing of flue gas velocity through horizontal

pipe. Cleaning of horizontal venting pipes is very

important to the efficiency of this boiler.
Clean the flue outlet throat as well as the inner chamber

of the flue tunnel (this is the hole that goes up into the

flue pipe). See Fig. 24.
NOTE: The exhaust probe sensing tip extends into

this same area. CARE MUST BE TAKEN NOT TO

DAMAGE THE ESP DURING CLEANING. Bending

of the ESP will make it difficult to remove if it should

become necessary. See Fig. 23.
Clean the boiler blower plate, sealing overlap. See Fig

24. Make sure there are no fly ash buildups that may

block the easy flow of flue gasses into the combustion

blower inlet hole. (A flashlight may be necessary.)
Cleaning the Tube Heat exchangers:
Three external cleaning rods allow scraping of the heat

exchange tubes with a simple in-and-out motion. See

picture on page 32.
This cleaning should be done at least once a week,

however it can be done more often as desired. The

cleaner the heat exchangers are, the more efficient the

boiler will be. It is best to perform during a low fire period

or when the fire is out. During high fire periods, the

cleaning rods may stick due to heat related expansion.

Combustion Blower Cleaning

Remove the combustion blower heat shield. There are

two latches that hold the shield in place (See Fig. 22).

Flip the latches up and pull the shield away from the

boiler. It can not be fully removed, it can only be moved

down over the wire until it hangs on the junction box.

CAUTION: Inspect flue pipes, flue pipe joints and

flue pipe seals regularly to ensure that smoke and

flue gases are not entering the home.

Fig. 23

Thumb Screws (3 Total)

Combustion

Blower Motor

Exhaust Probe

Heat Shield

Latch

Fig. 22

Fig. 24

Sealing Overlap

5” Double

Bladed Fan

Advertising