Client side connection parameterss – FieldServer FS-8700-40 User Manual

Page 11

Advertising
background image

FS-8700-40 SBT FSI Driver Manual

Page 11 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.1

Client Side Connection Parameters

Section Title
Connections
Column Title

Function

Legal Values

Port

Specify which port the device is connected to the FieldServer

P1-P8, R1-R2

6

Protocol

Specify protocol used

Cerberus,
SBT-FSI

Enhanced_Protocol

Enables legacy or enhanced protocol.. MXL panels do not currently
support Enhanced_Protocol, so this parameter must be set to “No” for
MXL. The parameter is normally set to “Yes” for XLS, but may be set to
“No” if problems are being experienced.

Yes (XLS)
No (MXL)

System_Type

Specifies Siemens Panel type

MXL, XLS

Block_Acks

7

Specifies if the driver uses block or individual command acks

Yes, No

Fire_Alarms_Hold*

Specifies if the driver should hold fire alarms until the system reset, or
clear on fire alarms going out

Yes, No

Baud*

Specify baud rate

19200
(Vendor
limitation)

Parity*

Specify parity

Even (Vendor
limitation)

Data_Bits*

Specify data bits

7

(Vendor

limitation)

Stop_Bits*

Specify stop bits

1

(Vendor

limitation)

Poll _Delay*

Time between internal polls

0-32000
seconds,

1

second


Example

// Client Side Connections
Connections
Port , Protocol , Baud

, Parity , Data_Bits , Poll_Delay

P1

, SBT-FSI

, 19200 , Even

, 7

, 0.100s

6

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available

on specific hardware.

7

Refer to the Advanced Driver Manual for usage. This function not enabled on standard driver.