Driver related map descriptor parameters, Timing parameters – FieldServer FS-8700-40 User Manual

Page 13

Advertising
background image

FS-8700-40 SBT FSI Driver Manual

Page 13 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.3.2 Driver Related Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch or store
data from

One of the Node names specified in Section 5.2

Block_Number

Starting module number within
panel. There are 256 points per
module.

1 – 256

Sub_Module

Sub module number for XLS
systems only

0 – 99

Component_Address

Component address for XLS
systems only

0 – 99

Length

Length

of

Map

Descriptor

specifies number of points. There
are 256 points per module.

1 – 10000

Msg_Type

Indicates

a

“poller”

Map

Descriptor or identifies the type
of event message this Map
Descriptor will handle. If this is
configured, the driver will store a
value that indicates the point type
of the event if the Data Array
used on the Map Descriptor is not
of a bit type

Poller; Fire_Alarm; Fire_Ack; Trouble; Trouble_Ack;
Super; Super_Ack; Secur; Secur_Ack; Status; Test;
Audible;

Reset;

Analog_Volts;

Analog_Sense;

Analog_Thres;

Entity_Arm_Disarm

8

;

Entity_Activate_Deact

9

Analog_Device

Indicates range of device data to
be requested by analogs

0 : devices 1-60
1 : devices 61-121
2 : devices 122-182
3 : devices 183-243
4 : devices 244-252

Block_Offset

This field allows you to set the
start address of a MXL or XLS
point in a Map Descriptor.

0 - 255

Entity_Types

Used to indicate the type of Entity
on the panel.. . Refer to Appendix
A.5 f
or more information

Inputs, Outputs, (If all elements are Input or Output)
OR specify each element of the entity individually
e.g. IOIOIOO

Entity_Energizations

Used to control the entity on the
panel. Refer to Appendix A.5 for
more information.

De-energize, Energize, (If all elements are Energize
or De-energize)
OR specify each element of the entity individually,
e.g. EDED---DED

5.3.3 Timing Parameters

Column Title

Function

Legal Values

Scan_Interval* Rate at which data is polled ≥0.001s , 1.0s

8

Refer to Appendix A.5

9

Refer to Appendix A.4

Advertising