FS-8700-40 SBT FSI Driver Manual

Page 16 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

5.3.5 Map Descriptor example 2 – Monitoring Analog Loop Devices

Analog devices on a loop can be monitored for detector voltage, sensitivity voltage and threshold voltage using three analog Map Descriptors:

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Block_Number , Length , Msg_Type

, Analog_Device , Scan_Interval

CD_Analog_Volts1

, Analog_Volts

, 0

, Rdbc

, Panel1

, 1

, 60

, Analog_Volts

, 0

, 300s

CD_Analog_Sens1

, Analog_Sense

, 0

, Rdbc

, Panel1

, 1

, 60

, Analog_Sense , 0

, 300s

CD_Analog_Thres1

, Analog_Thres

, 0

, Rdbc

, Panel1

, 1

, 60

, Analog_Thres , 0

, 300s

Note: If necessary, use more analog Map Descriptors with other Analog_Device numbers to poll other devices on the loop.

Scan Interval on analog
pollers may not be shorter
than 300s to prevent
flooding the Foreign
Systems Interface.

Use Float Data Arrays for
the analog Map
Descriptors to get the
full analog value.

0 : devices 1-60
1 : devices 61-121
2 : devices 122-182
3 : devices 183-243
4 : devices 244-252