Appendix A.5. Arming and De-Arming Entities

This example demonstrates the methodology to arm or disarm equipment on the MXL/XLS panel as per the SBT-FSI protocol specification. This relates to the
opcodes Disarm/manuallycontrol entity – opcode 0x77; Arm entity – opcode 0x78,

The configuration example in Section 4 can be modified as per the example below for Arming and De-arming Entities on the MXL Panel.

// Data Arrays
//

Data_Arrays

Data_Array_Name

, Data_Format

, Data_Array_Length

Counts_1

, Uint16

, 19

Arm_Disarm_Ent

, Bit

, 10

// Client Side Connections

//

Connections

Port

, Baud

, Parity

, Data_Bits

, Line_Drive_On

, Line_Drive_Off

, Enhanced_Protocol

, Protocol

, System_Type

P1

, 19200

, Even

, 7

, 0.001

, 0.001

, No

, Cerberus

, MXL

// Client Side Map Descriptors
//

Map_Descriptors

Map_Descriptor_Name

, Scan_Interval

, Data_Array_Name

, Data_Array_Offset

, Function

, Node_Name

, Block_Number

, Length

, Msg_Type

POLLER_1

, 2.0s

, Counts_1

, 0

, Rdbc

, Panel1

, 1

, 19

, Poller

Map_Descriptors

Map_Descriptor_Name

, Scan_Interval

, Data_Array_Name

, Data_Array_Offset

, Function

.Node_Name

, Block_Number

, Block_Offset

, Length

, Msg_Type

, Entity_Types

PNL_1_Arm_Disarm

, 0s

, Arm_Disarm_Ent

, 0

, Awt

, Panel1

, 1

, 1

, 10

, Entity_Arm_Disarm , Inputs

Map_Descriptors

Map_Descriptor_Name , Scan_Interval , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Block_Number , Block_Offset , Length , Msg_Type

, Entity_Types , Entity_Energizations

PNL_1_Arm_Disarm

, 0s

, Arm_Disarm_Ent , 0

, Awt

, Panel1

, 1

, 1

, 10

, Entity_Arm_Disarm , Outputs

, De-energize

Map_Descriptors

Map_Descriptor_Name , Scan_Interval , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Block_Number , Block_Offset , Length , Msg_Type

, Entity_Types , Entity_Energizations

PNL_1_Arm_Disarm

, 0s

, Arm_Disarm_Ent , 0

, Awt

, Panel1

, 1

, 1

, 10

, Entity_Arm_Disarm , Outputs

, Energize



The configuration example in Section 4 can be modified as per the example below for Arming and De-arming Entities on the XLS panel.

// Data Arrays
//

Data_Arrays

Data_Array_Name

, Data_Format

, Data_Array_Length

Counts_1

, Uint16

, 19

Arm_Disarm_Ent

, Bit

, 10

Advertising