FS-8700-40 SBT FSI Driver Manual

Page 6 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

Pinouts

FS Function RJ45 Pin# DB9F Pin# Cerberus Cable Pin Color
RX

1

2

14

Red

GND

4

5

16

Black

TX

8

3

13

Green

RTS

7

12

Brown

CTS

8

15

White

3.2

RS-232 Connection to the XLS Panel

Configure the NIM-1R

4

or NIM-1W for Foreign System Interface (FSI) by setting all of the switches in SW2

to open (or OFF).

The ports on the RPM can be configured for either RS-232 or RS-485, but not both together. Connection
to the RS-485 port of the RPM has not been tested and is not supported.

The FieldServer can be connected to either Port 1 or Port 3 on the XLS Panel as described in the
connection drawing. Pins 6 and 7 on the Port 2 Connector must be jumpered to enable RS-232 Port 3.

FieldServer

P1

1

8

2

3

4

1

6

7

8

5

10

9

RXD

TXD

RTS (Do not use)

CTS (Do not use)

GND

RXD

TXD

RTS (Do not use)

CTS (Do not use)

GND

Port 1

RS-232

Port 3

RS-232

2

3

4

1

6

7

5

Port 2

RS-485

RS-232 Port

FieldServer Part #

8917-16

Pigtail for RJ45

Port

Connect to one of the RS-232

Ports on the FieldServer

Brown

Blue/white

Orange/White

G

N

D

T

X

R

X

Pins 6 and 7
must be
jumpered to
enable Port 3

4

Note that NIM-1R is no longer supported by Siemens and is therefore considered to be legacy while NIM-1W is common.