Hardware connections, Using the nim-1r or nim-1w for mxl, Nim-1r connection – FieldServer FS-8700-40 User Manual

Page 5: Configure the nim-1r

Advertising
background image

FS-8700-40 SBT FSI Driver Manual

Page 5 of 32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

HARDWARE CONNECTIONS

3

3.1

Using the NIM-1R or NIM-1W for MXL

Configure the NIM-1R

3

or NIM-1W for Foreign System Interface (FSI) by setting all of the switches in SW2

to open (or OFF). See connection diagram below:

Connect the NIM-1R to an RS-232 port on the Fieldserver as depicted in the fiagram below (brown circle)

Connect the NIM-W to an RS-485 port on the FieldServer as depeicted in the diagram below.

FieldServer

P1

1

8

2

3

4

1

6

7

8

5

10

11

12

9

14

15

16

13

TB4

G

n

d

_

+

G

n

d

F

G

_

+

RS-485

Opto

Isolated

FS-8917-03
RJ45 to
DB9M
Connector

RJ45 CAT 5 Cable
FS8915-10

Cerberus Cable
P/N 555-193085

FS

-8

91

7-0

3

NIM-1R

Connection

3

Note that NIM-1R is no longer supported by Siemens and is therefore considered to be legacy while NIM-1W is common.