Passive Map Descriptors must be added for each event per panel to be monitored:

// Client Side Map Descriptors

Map_Descriptors

Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Block_Number , Length , Msg_Type
CD_Fire1

, Fire

, 0

, Passive

, Panel1

, 1

, 1024

, Fire

CD_Fire_Ack1

, Fire_Ack

, 0

, Passive

, Panel1

, 1

, 1024

, Fire_Ack

CD_Trouble1

, Trouble

, 0

, Passive

, Panel1

, 1

, 1024

, Trouble

CD_Trouble_Ack1

, Trouble_Ack

, 0

, Passive

, Panel1

, 1

, 1024

, Trouble_Ack

CD_Super1

, Super

, 0

, Passive

, Panel1

, 1

, 1024

, Super

CD_Super_Ack1

, Super_Ack

, 0

, Passive

, Panel1

, 1

, 1024

, Super_Ack

CD_Secur1

, Secur

, 0

, Passive

, Panel1

, 1

, 1024

, Secur

CD_Secur_Ack1

, Secur_Ack

, 0

, Passive

, Panel1

, 1

, 1024

, Secur_Ack

CD_Status1

, Status

, 0

, Passive

, Panel1

, 1

, 1024

, Status

CD_Test1

, Test

, 0

, Passive

, Panel1

, 1

, 1024

, Test

CD_Audible1

, Audible

, 0

, Passive

, Panel1

, -

, 1

, Audible

CD_Reset1

, Reset

, 0

, Passive

, Panel1

, -

, 1

, Reset

CD – Client Descriptor

Notes:

1

All passive Map Descriptors are optional. Specific Map Descriptors may be defined for particular events to be monitored as per the Msg_Type. Should
events happen for which no Map Descriptors are defined, error messages will occur on the FieldServer. It may therefore be useful to add dummy Map
Descriptors especially for ack responses to prevent nuisance error messages.

2

Passive Map Descriptors with Node_Name the same as the poller Map Descriptor will only be able to store events from a panel with the same Node_ID
e.g. Node_ID of 1 will only store events from panel 1. To store events from panel 2, it is necessary to add passive Map Descriptors with Node ID of 2 etc.
Do not add poller Map Descriptors for other panels.

3

Important Note about first alarm point and Data Array Offsets

Most SBT-FSI panels have device point numbers starting at one instead of zero. The FieldServer MXL driver reserves Data Array offset zero for points with
device numbers of zero although they are currently not used. Triggering the first alarm point on a MXL panel will thus result in a point status change at
Data_Array_Offset of one instead of zero.

Length specifies the number of points. There
are 256 points per module. A length of 1024
holds points for 4 modules.

Block Number specifies the
starting module number under
which points are mapped.

Node Name specifies the panel number