Connector Pinouts for RS-232 Ports

Wire Color

RJ-45

XLS Panel Port 1 (3)

Pin Signal Signal

Pin

Brown

1

Rx

TXD

2 (7)

White/Orange 8

Tx

RXD

1 (6)

Blue/white

4

GND

GND

3 (8)

3.3

FSI Connection Notes

It is possible to connect a MXL/XLS device to any RS-232 or RS-485 port. These ports simply need to be
configured for MXL/XLS in the configuration file.

The driver does not support MXL and XLS panels networked together.

One FSI panel may be connected per FieldServer port, but multiple panels may be connected per FSI. The
following diagram illustrates two possible connection configurations.

Configuration 1

– One FSI Panel per FieldServer per port, one Panel per FSI

FSI

FSI

Panel

Panel

Configuration 2

– One FSI Panel per FieldServer port, 3 panels connected in series to the FSI

FSI

Panel

Panel

Panel

FieldServer