Appendix A.6. Request ASD or Sensitivity

Data_Arrays

Data_Array_Name , Data_Format , Data_Array_Length
Current_ASD

, Uint16

, 60

Current_Sens

, Uint16

, 60

Map_Descriptors

Map_Descriptor_Name , Scan_Interval , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Block_Number , Length , Msg_Type
PNL_1_ASD

, 300s

, Current_ASD

, 0

, Rdbc , Panel1

, 1

, 60

, Current_ASD

PNL_1_Sens

, 300s

, Current_Sens

, 0

, Rdbc , Panel1

, 2

, 60

, Current_Sensitivity

The values stored are as follows:

Current_ASD

Current_Sensitivity

0

does not apply

does not apply

1

disabled

2.45%/foot

2

office

2.59%/foot

3

warehouse

2.72%/foot

4

lobby

2.86%/foot

5

computer room

3.00%/foot

6

dormitory

3.13%/foot

7

health care

3.27%/foot

8

garage

9

utility room

10 precious storage

11 hostile environment








Block_Number

sets

the

module number for which this
analog device data pertains

Data values will be stored for
device addresses from 0 to
Length which can be from 1
to 253