DATA ARRAY PARAMETERS

4

Data Arrays are “protocol neutral” data buffers for storage of data to be passed between protocols. It is necessary
to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.

Section Title
Data_Arrays
Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array

Up

to

15

alphanumeric
characters

Data_Array_Format

Provide data format. Each Data Array can only take on one
format.

5

Int16, Uint16, Bit

Data_Array_Length

Number of Data Objects. Must be larger than the data storage
area required by the Map Descriptors for the data being placed
in this array.

1-10, 000

Data_Array_Function Special function for Data Array – Refer to Appendix A.9.

Node_Status


Example

// Data Arrays

Data_Arrays

Data_Array_Name , Data_Format , Data_Array_Length
Event_Counts

, Uint16

, 19

Fire

, Bit

, 2048

Fire_UnAck

, Bit

, 2048

5

Format must be Uint16 or Int16 to see trouble codes.