2 facility power requirements and characteristics, Facility power requirements and characteristics – FUJITSU M3000 User Manual

Page 31

Advertising
background image

Chapter 2

Preparing to Install the Server

2-5

2.2.2.2

Facility Power Requirements and Characteristics

For proper redundancy, the facility must have two independent power sources. That
is, circuit breakers must be connected either to separate power company utility feeds
or to an uninterruptible power system (UPS). For power redundancy, the power
cables must not be connected to the same facility power source.

TABLE 2-3

Electrical Specifications

Item

Specification
100 to 120 VAC

200 to 240 VAC

Number of power cables

2 (1 cable for each power supply unit)

Power cord length

3 m/9.84 ft

Redundancy

1 + 1 redundant configuration

Input voltage

100 to 120 VAC

200 to 240 VAC

Rated current

*

* In a redundant configuration, the rated current per cable is half the value shown in

TABLE 2-3

.

4.80 A

2.59A

Frequency

50/60 Hz

Power consumption (maximum)

470 W

460W

Apparent power

480VA

517VA

Heat dissipation

1,603.7 BTU/hr (1,692 KJ/hr)

1,569.6 BTU/hr (1,656 KJ/hr)

Power factor

0.98 (full configuration)

0.89 (full configuration)

TABLE 2-4

Power Cords and Connector Shape

Destination

Power cable type

Connector shape

Japan

NEMA 5-15 125V15A

IEC 60320 C13

North America

NEMA L6-15 250V15A

China

GB 2099.1
250V15A

Hong Kong

IEC60320-C14
250V15A

South Korea

IEC 60320-C14
250V15A