FAN AND HEATER GENERATED ERRORS

The following is a list of errors that are generated with the fan and heater controller. Each fan and heater has there
own set of safeties which are listed below. You will need to inspect the controller associated with the error. Ex-
ample: If you get this error

it is telling you the problem is with Housing 1 (bottom most fan) High Limit.

Air Switch x Stuck

The air switch contacts have closed prior to the fan starting, indicating a freewheeling blade or improper setting
of the air switch. The message will distinguish between which fan caused the shutdown. This indicates that
12VDC has been lost to terminal J7-09 on the Fan/Heater board.

Fan x Loss of Airflow

This error message is displayed when airflow (air pressure) has been established but was lost for some
reason. This could happen if while during the dryers operation the grain has settled or shrinkage in the grain
columns causing a loss of air pressure in the plenum chamber.

Fan x No Airflow

Contacts in the air switch have never opened due to the fan not turning, or the air switch may need adjust-
ment. The message will distinguish between which fan caused the shutdown.

Flame Loss x

The flame sensor has failed to detect a burner flame which had been established but was lost for some reason
and there is a problem with the flame sensing circuitry or the dryer is not getting burner fuel. The message will