PNEG-951

to reset this error. This is caused from the motor operating with to much of a work load, which in turn uses
more current (amperage). If the problem reoccurs then check the motor to make sure it is not being over-
worked. You may need to call an electrician to measure the motors full load amps (FLA).

Grain Discharge Warning

The lid on the grain discharge box has opened, indicating that either the grain is not being taken away fast
enough from the discharge box or the take away auger system connected to the dryer may be causing the
problem. This can also occur if this safety looses 12VDC to terminal J2-05 on the I/O board.

Load Motor Overload

The motor overload has tripped on the Load Motor Overload located in the upper control box. This can occur
if this safety looses 12VDC to terminal J2-12 on the I/O board. Push the red button on the overload to reset
this error. This is caused from the motor operating with to much of a work load, which in turn uses more
current (amperage). If the problem reoccurs then check the motor to make sure it is not being overworked.
You may need to call an electrician to measure the motors full load amps (FLA).

Meter Rolls Failed

If you have the meter roll speed adjustment turned too low (not turning), this will cause this error message. It
also could indicate that you have a defective meter roll sensor, the metering roll drive system has failed to turn
or broken chain or jammed metering roll is a possibility. This can occur if the input is not receiving a 5 volt
pulse on terminal J3-03 on the I/O board.

Out of Grain

The dryer has run low on grain, and the out of grain timer has timed out, shutting the dryer down. The unload
auger will continue to run so it can clean out the remaining grain before shutting down.