INSTALL THE DRAIN(S)

An external or an internal drain must be attached

to the primary drain connector. A secondary drain

is supplied if required by state and local codes. Refer

to the local codes for proper installation of the drains.

If the secondary drain is not used, seal its drain port

with a 3/4” MNPT plug.

External Drain

Attach a 90° PVC elbow to the unit’s female 3/4

NPT

drain connector. Use the other end of the elbow to run
a 3/4

Sch. 40 PVC pipe through the knockout holes of

both the wall plenum and the architectural louver to the

outside. Seal the gap between the plenum hole and PVC

tube. See the Installation Instructions in the RAVAL1.

Internal Drain

Attach PVC to the unit’s female 3/4

NPT drain

connector. See the Installation Instructions

in the RAVAL1. Local codes may apply.

2

DUCTWORK

Prepare the closet ductwork for later connection

to the case.

The total flow rate (CFM) and external static pressure

(ESP) available can be estimated from the chart below.

Use these charts to select your fan speed setting. The
collar on top of the case accepts standard 10

duct.

Pull all duct tight. Extra duct slack can greatly increase

static pressure.

NOTICE:

Flex duct can collapse and cause

airflow restrictions. Do not use flex duct for 90° bends

or unsupported runs of 5 ft. or more.

3

Installation Instructions

Your airflow should be balanced based on many

factors, such as available ESP, room CFM, and ductwork.

Consult an HVAC engineer for proper applications.

External static pressure (ESP) can be measured with a

manometer or pitot tube. Once this ESP is established,

you can calculate the CFM using the above chart.

CFM Recommendations

9,000 BTU

12,000 BTU

18,000 BTU

390 415 440 440 465 490 435 485 535

• = Recommended Mid Range

Higher CFMs tend to increase Sensible capacity,

enhance room circulation and increase duct noise,

while lower CFMs tend to increase Latent capacity

and reduce noise.

Side View

Inside wall

Female drain
fitting

3

4

PVC

90° Elbow

PVC

(External drain)

PVC

(Internal drain)

Side View

Inside wall

Female drain
fitting

3

4

Airflow – CFM @ 230 Volts and @ 265 Volts

Indoor Fan CFM

DUCT SELECT SWITCH

UP

DOWN

ESP

(in. water)

High

CFM

Medium

CFM

Medium

CFM

Low

CFM

0.0

0.1

0.2

0.3

0.4

520

500

480

440

400

460

415

370

265

160

460

415

370

265

160

360

290

220

-

-

0.0

0.1

0.2

0.3

0.4

590

570

550

480

410

500

465

430

345

260

500

465

430

345

260

380

325

270

-

-

0.0

0.1

0.2

0.3

0.4

600

585

570

510

450

520

485

450

375

300

520

485

450

375

300

400

340

280

-

-

AZ85(H/E)0

9

AZ85(H/E)1

2

AZ85(H/E)1

8

To correct for 208 volts: 0.91

19