Things that are normal, Minute delay “click, Compressor protection – GE AZ85H12DAC User Manual

Page 24

Advertising
background image

24

Consumer

Support

Troubleshooting

Tips

Care

and

Cleaning

Operating

Instructions

Safety

Instructions

Normal Operating Sounds

You may hear a pinging noise caused by water being

picked up and thrown against the condenser on rainy

days or when the humidity is high. This design feature

helps remove moisture and improve efficiency.

You may hear relays click when the controls cycle

on and off or are adjusted to change the room

temperature.

Water will collect in the base pan during high humidity

or on rainy days. The water may overflow and drip

from the outdoor side of the unit.

The indoor fan runs continuously when the unit is

operating in the cooling mode, unless the fan switch

behind the case front panel is set at fan cycle (up).

This will cause the fan to cycle on and off with

the compressor. You may also hear a fan noise

stop and start.

You may notice a few minutes delay in starting

if you try to restart the Zoneline too soon after

turning it off or if you adjust the thermostat right after

the compressor has shut off. This is due to a built-in

restart protector for the compressor that causes

a 3-minute delay.

During the defrost cycle, both indoor and outdoor

fans stop and the compressor will operate in the

cooling mode to remove frost from the outdoor coil.

After defrost, the unit will restart in electric heat to

quickly warm the room to the desired comfort level.

To protect the compressor and prevent short cycling,

the unit is designed to run for a minimum of 3 minutes

after the compressor starts at any thermostat setting.

Things that are normal.

3-Minute

Delay

“CLICK”

S

I

L

E

N

C

E

COMPRESSOR

PROTECTION

Advertising
This manual is related to the following products: