Gravimetric

Blender

3.3.3 Input & Output monitor

The input & Output screen menu (F1) ‘controller / digital I/O monitor’ displays all digital

input and output lines. Every object in the screen can be selected by using the arrow-keys.

When a output line is selected and <ENTER> is given the digital output will toggle. The

operator has control of the digital outputs when the controller is in ‘manual mode’.

3.4

Adjustment of the gravimetric blender

The controller has some system-parameters. These parameters must be entered during the

installation of the GraviMaster. The controller uses these parameters to read the weigh bin

signal correctly, to open the weigh bin-valve, control the dispense-valves or motors etc.

3.4.1 Calibration of the weigh bin

The controller uses two known (entered) calibration-points to calculate a weighline. The

controller uses this line to fi nd a weight by every input-signal. The two calibration-points

must be entered by the operator by the menu (F1) ‘controller / calibration / loadcell’.

The calibration-procedure of the loadcell has two steps. Extra information is given to the

operator by every step. This information is displayed at the top of the screen. First be sure

that the weighbin is empty and press (F3). The weight of the empty weighbin is measured

and stored by the controller. Next step is to fi ll the weighbin with a reference-weight and be

sure that the input fi eld on the terminal has the same value. Now press (F3) again and the

second calibration-point is measured and stored. The calibration-procedure is now ready.

IMPORTANT

The second calibration-point must be greater then the fi rst one.

3.4.2 Tare of the weighbin

Due to temperature, age, overload etc. it is possible that the weighline of the controller

‘moves’. When the line has moved a zero-weight will be displayed that isn’t zero. To move

the weightline back it is possible to start a new calibration procedure. But the calibration-

procedure takes a lot of time and the weightline is correct (it only moved). The tare-function

moves the line back to its zero-point. To start the tare function enter menu (F1) ‘controller

/ calibration / loadcell-tarration’.