4 message monitoring, 5 ethernet driver, Chapter 3 – configuration – GE GEH6505A User Manual

Page 14: Power leader™ ethernet gateway, 3–4 message monitoring, 3–5 ethernet driver

Advertising
background image

POWER LEADER™ Ethernet Gateway

Chapter 3 – Configuration

10

Option Number:

Valid Entries at Prompt:

1 = RS485 Port 1
3 = RS485 Port 2
5 = RS485 Port 3
7 = RS485 Port 4

0 = 1200 baud

4 = 19200 baud

1 = 2400 baud

5 = 38400 baud

2 = 4800 baud

6 = 57600 baud

3 = 9600 baud

2 = RS485 Port 1
4 = RS485 Port 2
6 = RS485 Port 3
8 = RS485 Port 4

Data Bits:

0 = 7 data bits
1 = 8 data bits

Stop Bits:

0 = 1 stop bit
1 = 2 stop bits

Parity:

0 = None
1 = Even
2 = Odd

Table 5. RS485 Port Settings .

1. Follow the procedure outlined in Section 3-1

to configure the Gateway.

2. At the Configuration menu, select the option

number, then press

<ENTER>

. At the prompt,

enter the new setting, then press

<ENTER>

. For

options 1, 3, 5, and 7, enter the new setting

from the options in Table 5, then press

<ENTER>

. For options 2, 4, 6, and 8, enter each

new parameter as prompted, using the correct

entries from Table 5. If you enter an invalid

value, the following message display:

Press

<ENTER>

to return to the Configuration

menu.

NOTE: Pressing <ESC> while entering a new value for a
setting discards the changes and redisplays the
Configuration menu.

3. Follow steps 5 and 6 of Section 3-1 to save any

changes and exit configuration mode.

3–4 Message Monitoring

For diagnostic purposes, you may want to monitor

message traffic across the RS485 ports. This can be

done on a terminal connected to the RS232 port.

You may monitor messages on any single RS485

port or on all four ports simultaneously.
Selecting menu item 14 allows you to select whether

or not messages are sent to the RS232 port in

monitor mode and which RS485 ports are to be

monitored. The following prompt appears:

Enter your selection from the above choices.

3–5 Ethernet Driver

Menu item 10 permits the Ethernet driver to be

selected. Most systems utilize DIX Ethernet; a

handful use IEEE Ethernet. The Gateway defaults

to the DIX Ethernet driver. If your network does not

function under DIX Ethernet and you have

eliminated all other potential sources of trouble,

change the driver setting to IEEE Ethernet and retry

communications. If this does not resolve the

problem, contact Customer Service.

Advertising