1–4 Specifications

The specifications of the Ethernet Gateway are

listed in Table 2.

Parameter

Value

Control power

90–132 Vac or 180–264 Vac,
47–63 Hz; autoranging
Power supply =150 VA min
(contact your GE sales
representative for additional
voltage options.)

Modbus communications

Four RS485 ports, 1200 baud,

2400 baud, 4800 baud, 9600
baud and 19.2 Kbaud.

Ethernet communications

One PCL-843 16-bit Ethernet
card; supports 10BaseT or
10Base2 transport mediums.

Standards

UL Listed
CSA Certified

508 & 840
C22.2 No. 14

Table 2. POWER LEADER Ethernet Gateway specifications.

1–5 Environmental Requirements

The environmental requirements of the Ethernet

Gateway are listed in Table 3.

Parameter

Value

Operating temperature

0° C to +50° C

Storage temperature

–20° C to +80° C

Relative humidity

10% to 95% noncondensing

Vibration response and

endurance

IEC 255–21–1

Severity Class 1

Fast transient surge

ANSI C37.90.1

Radiated EMI withstand

ANSI C37.90.2

Electrostatic discharge

IEC 801–2

Severity Class 4

Table 3. POWER LEADER Ethernet Gateway environmental

requirements.

1–6 Terminology

Following are definitions of some of the terms used

in this document.

POWER LEADER

– The GE family of comprehensive

power management devices and system software used
to minimize downtime and overall power cost.

PMCS

– Power Management Control System software.

SCADA (supervisory control and data acquisition)

– A group

of systems including power management and control
systems.

DCS (distributed control system)

– A group of systems

including building automation and status
monitoring systems.

Ethernet

– An open, industry-standard, high-perform-

ance network communications protocol that operates
on 10BaseT or 10Base2 transport mediums and
yields communications rates up to 10 megabits per
second.

Modbus RTU (Remote Terminal Unit)

– An open, industry-

standard, high-performance network communica-
tions protocol developed by Modicon/AEG
Schneider Automation.

Modbus-compatible device

– Any device equipped with a

Modbus RTU communications port.

Modbus master

– A host computer running PMCS

software.

RS485/EIA485

– A physical standard for multi-drop,

high-speed, noise-tolerant communications over a
twisted pair network; often used with the Modbus
RTU protocol.

Commnet

– A GE proprietary communications network

standard.

Commnet-compatible device

– Any meter, relay, trip unit, or

other device equipped with a commnet commu-
nications port.

Commnet segment

– A group of one to four commnet-

compatible devices (including at most one waveform-
capturing meter) with all communication ports wired
to a single Concentrator commnet port.