TM-353 Page 11

Syncrowave 250

3-10. Electrical Service Guide

All values calculated at 60% duty cycle.

NOTE

60 Hertz Models

Without Power Factor

Correction

With Power Factor Correction

Input Voltage

200

230

460

575

200

230

460

575

Input Amperes At Rated Output

85

74

37

30

55

48

24

19

Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes

125

110

60

45

80

70

35

30

Min Input Conductor Size In AWG/Kcmil

4

6

10

10

8

8

12

14

Max Recommended Input Conductor Length
In Feet (Meters)

173

(53)

158

(48)

291

(89)

455

(139)

86

(26)

114

(35)

186

(58)

189

(48)

Min Grounding Conductor Size In AWG/Kcmil

6

6

10

10

8

8

12

14

Reference: 1996 National Electrical Code (NEC)

S-0092-J

50 Hertz Models

Without Power Factor Correction

With Power Factor

Correction

Input Voltage

220

260

380

415

520

220

380

415

Input Amperes At Rated Output

77

65

45

41

33

64

37

34

Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes

125

100

70

60

50

90

60

50

Min Input Conductor Size In AWG/Kcmil

6

6

8

8

10

6

10

10

Max Recommended Input Conductor Length
In Feet (Meters)

145

(44)

202

(62)

291

(89)

347

(106)

372

(113)

145

(44)

291

(89)

347

(106)

Min Grounding Conductor Size In AWG/Kcmil

6

8

8

10

10

6

8

10

Reference: 1996 National Electrical Code (NEC)

S-0092-J