VERTICAL (THROUGH-THE-ROOF)
APPLICATIONS

This gas fireplace has been approved for,
• Vertical installations up to 40' (12m) in height. Up to a 10'

(3m) horizontal vent run can be installed within the vent
system using a maximum of two 90° elbows. See Figure
18.

Figure 18 - Support Straps for

Horizontal Runs

VENT INSTALLATION

Figure 19 - Maximum Elbow Usage

• Up to two 45° elbows may be used within the horizontal

run. For each 45° elbow used on the horizontal plane,
the maximum horizontal length must be reduced by 18"
(450mm).

Example: Maximum horizontal length

No elbows = 10’ (3m)

1x45° elbows = 8.5’ (2.6m)

2x45° elbows = 7’ (2.1m)

• A minimum of an 8' (2.5m) vertical rise is required.
• Two sets of 45°elbows offsets may be used within the

vertical sections. From 0 to a maximum of 8' (2.5 m) of
vent pipe can be used between elbows. See Figure 19.

• The maximum angular variation allowed in the system is

270°. See Figure 19.

• The minimum height of the vent above the highest point

of penetration through the roof is 2' (610mm).

1

2

3

4

Example:

Elbow 1 = 90°

Elbow 2 = 45°

Elbow 3 = 45°

Elbow 4 = 90°

Total Angular Variation = 270°

NOTE: Horizontal sections of this vent system require
a minimum of 3" clearances to combustibles at the top
of the fl ue and 1" clearance at the sides and bottom
until the fl ue penetrates the outside wall. A minimum
1" clearance all around the fl ue is acceptable at this
point of penetration.

Vertical sections of this vent system require a
minimum of 1" clearance to combustibles on all sides
of the pipe.