Troubleshooting – Monessen Hearth Direct Vent Gas Fireplace KHLDV SERIES User Manual

Page 39

Advertising
background image

73D0024

39

TROUBLESHOOTING

STANDING PILOT IGNITION

SYMPTOM POSSIBLE

CAUSE

ACTION

4. Frequent pilot outage

problem.

5. The pilot and main

burner extinguish
while in operation

6. Glass

Soots

7. Flame burn blue and

lifts off burner (ghost-
ing)

A. Pilot flame may be too high or

too low, causing pilot safety
to drop out

A. Inner vent pipe leaking

exhaust gases back into
system

B. Horizontal vent improperly

pitched

C. Improper vent cap installation

A. Flame impingement on logs

A. Insufficient oxygen being

supplied

A. Clean and adjust the pilot flame for maximum flame impinge-

ment on thermocouple.

A. Check for flue product leak. Replace defective pipe section.

B. Check horizontal-venting piping is running upward 1/4" per foot.

Do not run the pipe level or downward.

C. Check for proper installation and freedom from debris or

blockage.

A. Install log set per the instructions
Inspect the injector and air intake area. Make sure this area does

not have any blockage from debris and clean.

Check gas supply.

A. Ensure that the vent cap is installed properly and free of debris.

Ensure that the vent system joints are tight and have no leaks.
Ensure that no debris has been blocking the inner air intake at the
bottom back of the combustion chamber. Ensure that the glass is
properly secure and latch.