2. protective functions, 2-1. current control – Sanyo CM1972 User Manual

Page 45

Advertising
background image

7-2. Protective Functions

The numerical values such as temperature, frequency, time and current in parentheses are an example
of CM3172 and the values are different from the other models.

NOTE

7-2-1. Current Control

The operating current may rise as a result of causes including increasing cooling loads or decreases in power

voltage. In these cases, the operating frequency is automatically reduced, or operation is stopped, in order to control

the operating current so that it is (20 A) or less.

The operating frequency is reduced automatically, or operation is stopped, in order to control the operating

current so that it is at or below the values shown in the table below.

(20A)

Power breakers and fuses will not be tripped.
Operation can continue during this period with somewhat reduced cooling capacity.
Operation at normal capacity is restored when the cause of the current rise is eliminated.

Description of function



Example of operation for cooling

Frequency

Frequency

Current

Stops operation

Approx.3 minutes

Power Point C

Point B

Point A

(20A)

(17A)

(16.6A)

Target

frequency

Operates at the target frequency at Point A and below.

Stops increases to the frequency between Points A and B.

Reduces the frequency by 1 Hz per 0.5 seconds when Point B is exceeded.

Stops operation, and restarts it appoximately 3 minutes later, if Point C is exceeded.

(May operate when sudden voltage fluctuations occur. Indicates trouble.)

As a result:

(1) Automatic frequency control

COOL

(20.0)
(17.0)

Point C (peak cut trip)
Point B (Hz reduction)
Point A (Hz increase prohibit)

(16.6)

45