5

Install the indoor unit more than 3.3' (1 m) away from any

antenna or power lines or connecting wires used for tele-

vision, radio, telephone, security system, or intercom.

Electrical noise from any of these sources may affect

operation.

install in a sturdy manner to avoid increased operating

noise.

Table 3

* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

Max.

Max. Allowable Total

Limit of

Limit of Elevation

Required Amount

Allowable

Tubing Length Total Tubing Length

Difference of

Additional

Model

Tubing Length

at shipment

(L1+L2+L3) or

(H1, H2, H3, H4)

Refrigerant

per unit

(L1+L2+L3) or

(L1+L2+L3+L4)

(ft.)

(oz./ft.)

*

(ft.)

(L1+L2+L3+L4)

(ft.)

(ft.)

CM1972/CLM1972

82

150 (L1+L2+L3)

150 (L1+L2+L3)

50

CM2472/CLM2472

82

150 (L1+L2+L3+L4)

200 (L1+L2+L3+L4)

50

0.22

CM3172/CLM3172

100

150 (L1+L2+L3+L4)

230 (L1+L2+L3+L4)

50

0.22