No voltage on circuit board

(6) Electric expansion valve

When replacing the electric expansion valve and coil, be sure to attach the connectors in the correct positions.

Labels are applied to the valve body and coil, corresponding to the connector colors, to identify them.

Controller check

Voltage varies

0 ohm

No temperature change

Temperature changes

Replace the coil.

Open and close the

electric expansion valve

by hand to check it.

Replace the electric

expansion valve.

This part is normal.

Check elsewhere.

Check the illumination

of the red Power Lamp.

Replace the controller.

Check the coil resistance.

Use a multi-meter to measure the voltage (12 V).

Model No.

Sequence

CM1972

CM2472

CM3172

MV0

MV1

When the power is turned ON, the needle will move in the

following seguence in approximately 10 to 20 seconds for

each point.

Check the resistance between the gray lead

wire and the other wires.

Resistance is OK if it is 46 + / – 4ohm at 68 °F

Cool the main unit with

a damp cloth or other

means while welding.

When applying

vacuum, use the

special service magnet

and rotate at least 5

revolutions

counterclockwise to

fully open the electric

expansion valve.

*1

Approx. 46 +/– 4 ohm

NOTE

*1 If you have manually checked the electric expansion valve, be sure to reapply the outdoor power after you have

replaced the wiring. (The position of the elecric expansion valve will changed.)

MV2

MV0

MV1

MV2

MV3

Use the special service magnet and

rotate 5 revolutions clockwise to fully

close the valve.

Then start the unit and measure the

temperature at the inlet and outlet

tubes of the electric expansion valve.

If the temperature difference is large,

the valve is closed.

Then rotate 5 revolutions

counterclockwise to open the valve.

Operation is normal if the temperature

difference between the 2 tubes drops.