3. checking the outdoor system – Sanyo CM1972 User Manual

Page 49

Advertising
background image

8-3-1. Checking the outdoor unit

8-3. Checking the Outdoor System

Work procedure

Apply 220 V AC between terminals L1 and L2 on the
outdoor unit terminal plate.

•

Short-circuit the T-RUN terminal to the COM terminal
of TEST/T-RUN terminals.

•

The LED (red) on the control board must illuminate.

•

The compressor and fan motor must turn ON.
(They turn ON about (70) seconds later after the power
is turned ON.)

•

No.

1

2

Check items (unit operation)

NOTE

If the above check items are okay, but the outdoor unit does not operate, there may be a faulty
connection between the indoor unit and the outdoor unit.