Nc class stainless, Marley, Specifications: base – SPX Cooling Technologies SS-NC-08A User Manual

Page 10: Cooling tower

Advertising
background image

Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Base

10

10.0 Access:

10.1 A large stainless steel, rectangular

access door shall be located on both

end panels for entry into the cold

water basin. Doors shall provide

access to the fan plenum area to facili-

tate inspection and allow maintenance

to the fan drive system.

11.0 Cold Water Collection Basin:

11.1 The collection basin shall be heavy-

gauge S300 stainless steel, and shall

include the number and type of suction

connections required to accommodate

the outflow piping system shown on

the plans. Suction connections shall be

equipped with stainless steel debris

screens. A factory-installed, float-oper-

ated, mechanical make-up valve shall

be included. An overflow and drain

connection shall be provided in each

cell of the cooling tower. The basin

floor shall slope toward the drain to

allow complete flush out of debris and

silt which may accumulate. Towers of

more than one cell shall include stain-

less steel flumes for flow and equal-

ization between cells. The basin shall

be accessible and maintainable while

water is circulating.

The access doors on NC8301 and

NC8302 towers are 76cm wide by

84cm high. On NC8303 thru NC8312

the access doors are 122cm high.

Small access doors are prohibitive

and discourage maintenance, which

in turn can impact your operation.

Specifying the size of the door will

cause some bidders to take excep-

tion, alerting you to a potential

maintenance headache. Two doors

are standard on all NC Class tow-

ers—one in each endwall.

The NC tower design offers side-

suctions, side-outlet sumps, and

bottom outlets to accommodate

a significant variety of piping schemes. Unless so specified, the tower

you may be asked to approve may only be available with one type of

suction connection, requiring you to redesign your piping layout.