Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Options

13

Access Door Platform:

11.2 Add the following paragraph in the

Access section: There shall be an

access platform at the base of the

tower extending from the vertical lad-

der to the endwall access door. The

platform shall be galvanized steel bar

grating, supported by galvanized steel

framework attached to the tower.

The platform shall be surrounded by a

guardrail, kneerail, and toeboard.

Plenum Walkway

11.2 Add the following paragraph in the

Access section: Provide a factory-

installed, galvanized steel bar grating

walkway extending from one endwall

access door to the other endwall. This

walkway shall be supported by a gal-

vanized steel framework, and the top

of the grating shall be at or above the

cold water basin overflow level.

Interior Mechanical Equipment

Access Platform

NC8303 thru NC8309

11.2 Add the following paragraph in the

Access section: A factory-installed,

elevated galvanized bar grating plat-

form convenient to the care and main-

tenance of the tower's mechanical

equipment shall be provided.

Interior Mechanical Equipment

Access Platform

NC8310 thru NC8312

11.2 Add the following paragraph in the

Access section: An internal ladder

shall extend upward from the plenum

walkway to an elevated galvanized

bar grating platform convenient to the

care and maintenance of the tower's

mechanical equipment. The platform

shall be surrounded by a sturdy guard-

rail and kneerail system.

Where towers are installed on an elevated grillage or piers, it is

often difficult to get to—and through—the access door conve-

niently. This platform provides easy, safe and comfortable access

to that door. It also extends beyond the door to provide ready

access to the optional Control System. See drawing on page 12.

Outside the tower, stainless steel platform material is not normal-

ly considered necessary. If you air quality is sufficiently poor to

warrant stainless steel, change the specification wording accord-

ingly.

NOTE

OSHA and other concerned authorities are in the process

of developing guidelines regarding the safety procedures and
protective equipment that should be provided maintenance per-
sonnel who are required to go inside cooling towers. We feel it
advisable to provide for as much maintenance as possible from
outside the cooling tower and, to that end, offer such options as
Guardrail and Ladder—pg 11, Ladder Extension—pg 11, Ladder
Safety Cage—pg 11, Access Door Platform—pg 13, and Motor
Out of the Airstream—pg 18. Such interior convenience options
as Plenum Walkway—pg 13, that are offered are not meant as
an invitation to perform inside maintenance. They are intended
solely to maximize the comfort and safety of maintenance per-
sonnel during the performance of any inside work may become
necessary.