Convenience and Safety Options

Guardrail and Ladder:

11.2 Add the following paragraph in

the Access section: The top of the

tower shall be equipped with a sturdy

guardrail, complete with kneerail and

toeboard, designed according to OSHA

guidelines and factory welded into

subassemblies for ease of field instal-

lation. Posts, toprails and kneerails

shall be 38mm square tubing. The

guardrail assembly shall be hot dipped

galvanized after welding and capable

of withstanding a 890N concentrated

live load in any direction. Posts shall

be spaced on centers of 2.4m or less.

A 46cm wide aluminum ladder with

76mm I-beam side rails and 32mm

diameter rungs shall be permanently

attached to the endwall casing of the

tower, rising from the base of the

tower to the top of the guardrail.

Ladder Extension:

11.2 Add the following to the end of the

above paragraph: Provide a ladder

extension for connection to the foot

of the ladder attached to the tower

casing. This extension shall be long

enough to rise from the roof (grade)

level to the base of the tower. The

installing contractor shall be respon-

sible for cutting the ladder to length;

attaching it to the foot of the tower lad-

der; and anchoring it at its base.

Ladder Safety Cage:

11.3 Add the following paragraph in the

Access section: A heavy gauge galva-

nized steel safety cage shall surround

the ladder, extending from a point

approximately 2m above the foot of

the ladder to the top of the guardrail.

Ladder Safety Gate:

10.3 Add the following paragraph in the

Access section: A galvanized steel,

self-closing gate shall be provided at

the guardrail level of the ladder.

The NC Class cooling tower has been

designed to minimize the need for mainte-

nance personnel to get on top of the tower

to perform maintenance and inspections.

For the comfort and safety of your operat-

ing personnel, we recommend that you

specify a ladder and guardrail—and that

you require it of all bidders! Although not

required for safe operation by OSHA many

user's own safety rules may dictate these

options.

Outside the tower, stainless steel guardrail

material is not normally considered necessary. If you air quality is

sufficiently poor to warrant stainless steel, change the specifica-

tion wording accordingly.

Many towers are installed such that the base of the tower is 61cm

or more above the roof or grade level. This makes it difficult to

get up to the foot of the attached ladder. The ladder extension

alleviates this problem. Marley ladder extensions are available in

standard 1.5m and 3.3m lengths.

To meet OSHA guidelines, towers whose fan decks are 6m or

more above roof or grade, and which are equipped with lad-

ders, should have safety cages surrounding the ladders, but with

approximately 2m clear headroom.

Outside the tower, stainless steel safety cage material is not

normally considered necessary. If you air quality is sufficiently

poor to warrant stainless steel, change the specification wording

accordingly.

A galvanized self-closing gate located at the guardrail level of

the fan deck, exterior motor access platform and access door

platform. Stainless steel is available with the stainless guardrail

option.