Nc class stainless, Marley, Specifications: base – SPX Cooling Technologies SS-NC-08A User Manual

Page 8: Cooling tower

Advertising
background image

Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Base

8

LOUVERS

DRIFT ELIMINATOR

separate from fill

on some models

FILL

7.0

Fill, Louvers and Drift Eliminators:

7.1

Fill shall be film type, thermoformed

of 0.40mm thick PVC, with louvers

formed as part of each fill sheet. Fill

shall be suspended from hot dip gal-

vanized structural tubing supported

from the tower structure, and shall be

elevated above the floor of the cold

water basin to facilitate cleaning. Air

inlet faces of the tower shall be free of

water splash-out. Fill shall be capable

of withstanding a hot water tempera-

ture of 52°C.

7.2

Drift eliminators shall be PVC, triple-

pass, and shall limit drift losses to

0.005% or less of the design water

flow rate.

Louvers integral with the fill keep the flowing water within the confines

of the fill. The separate external louvers used by others permit water to

escape the fill and form ice or produce an unsightly situation adjacent

to the tower and waste water. If you

plan to use your tower in the win-

tertime, particularly for free cooling,

integral louvers will put your operat-

ing concerns to rest. Integral louvers

offer the best available technology for

winter operation and water conserva-

tion.

Fill options are available for hot water

temperatures up to 60°C.

Drift rate varies with design water

loading and air rate, as well as drift

eliminator depth and number of

directional changes. A drift rate of

0.001% is readily available in standard

configuration without premium cost. If a

lower rate is required, please discuss with your

Marley sales representative.

Keep in mind…
• Drift for towers with three-pass high efficiency eliminators constitute a

small percentage of water usage.

• Unlike thermal performance, drift rates are not certified and field drift

tests are cost prohibitive for most applications.

• Drift rates below 0.001 are difficult to measure in the field.

• Certain water treatment chemicals can impact the drift rate.