cold-water temperature. The application

must be able to handle very cold water

while VFD is in a by-pass mode. Operator

controls shall be mounted on the front of

the enclosure and shall consist of start

and stop control, bypass/VFD selection,

Auto/Manual selections, manual speed

control. To prevent heating problems

in the cooling tower fan motor and to

assure proper gear reducer lubrication

the VFD system shall de energize the

motor once 25% motor speed is reached

and cooling is no longer required. The

cooling tower manufacturer shall supply

VFD start-up assistance. Tower vibration

testing throughout the speed range is

required to identify and lockout any natu-

ral frequency vibration levels which may

exceed CTI guidelines.

Marley Premium VFD System

6.4 Add the following paragraph in

the Mechanical Equipment section

when VFD is used as a stand alone

system:

A complete UL listed Variable

Speed Drive system in a IP52 indoor or

IP14 outdoor enclosure shall be provided.

The VFD shall use PWM technology with

IGBT switching and integrated bypass

design. VFD output switching shall not

cause mechanical issues with gearbox

teeth or drive shafts. The VFD shall catch

a fan spinning in the reverse direction

without tripping. The panel shall include

a main disconnect with short circuit pro-

tection and external operating handle,

lockable in the off position for safety.

The system shall include a solid state,

PI temperature controller to adjust fre-

quency output of the drive in response

to the tower cold-water temperature.

The temperature of the cold water and

set point shall be displayed on the door

of the control panel. The bypass shall

include a complete magnetic bypass

circuit with capability to isolate the VFD

when in the bypass mode. Transfer to

the bypass mode shall be automatic in

the event of VFD failure or for specific

trip conditions allowing safe transfer of

utility voltage to the motor. Automatic

bypass with an earth ground condition is

not allowed. The bypass contactor shall

be cycled on and off while operating in

bypass, to maintain the set-point temper-

ature of the cold water. The drive design