Nc class stainless, Marley, Specifications: options – SPX Cooling Technologies SS-NC-08A User Manual

Page 16: Cooling tower

Advertising
background image

Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Options

16

in quantities and locations as indicated

on the drawings. An overflow and drain

connection shall be provided in each

cell of the cooling tower. The basin

floor shall slope toward the drain to

allow complete flush out of debris and

silt which may accumulate. Towers of

more than one cell shall include stain-

less steel flumes for flow and equal-

ization between cells. The basin shall

be accessible and maintainable while

water is circulating.

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4 Add the following paragraph in the

Mechanical Equipment section when

VFD is used with customers Building

Management System:

A complete UL

listed Variable Speed Drive system in a

IP10 indoor, IP52 indoor or IP14 outdoor

enclosure shall be provided. The VFD

shall use PWM technology with IGBT

switching and integrated bypass design.

VFD out put switching shall not cause

mechanical issues with gearbox teeth

or drive shafts. The VFD shall catch a fan

spinning in the reverse direction without

tripping. The panel shall include a main

disconnect with short circuit protection

and external operating handle, lockable

in the off position for safety. The VFD

system shall receive a speed reference

signal from the Building Management

System monitoring the tower cold-water

temperature. As an option to receiving

the speed reference signal from a build-

ing management system, the drive must

have the capability to receive a 4-20 ma

temperature signal from an RTD trans-

mitter. The VFD shall have an internal PI

regulator to modulate fan speed main-

taining set point temperature. The drive's

panel display shall be able to display the

set-point temperature and cold-water

temperature on two separate lines. The

bypass shall include a complete mag-

netic bypass circuit and with capability

to isolate the VFD when in the bypass

mode. Transfer to the bypass mode shall

be manual in the event of VFD failure.

Once the motor is transferred to the

by-pass circuit the fan motor will run at

constant full speed. The bypass circuit

will not modulate ON and OFF based on

Marley Variable Speed Drive systems are designed to combine absolute

temperature control with ideal energy management. The cooling tower

user selects a cold water temperature and the drive system will vary the

fan speed to maintain that temperature. Precise temperature control is

accomplished with far less stress to the mechanical equipment compo-

nents. The improved energy management provides fast payback to the

user.