Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Options

15

Vibration Limit Switch:

6.5

Add the following paragraph in the

Mechanical Equipment section: A

single-pole, double-throw vibration

limit switch in a IP56 housing shall be

installed on the mechanical equipment

support for wiring into the fan motor

shutdown circuit. The purpose of this

switch will be to interrupt power to the

motor in the event of excessive vibra-

tion. It shall be adjustable for sensitiv-

ity, and shall require manual reset.

Basin Heater:

11.2 Add the following paragraph in the

Cold Water Basin section: Provide a

system of electric immersion heaters

and controls for each cell of the tower

to prevent freezing of water in the

collection basin during periods of shut-

down. The system shall consist of one

or more stainless steel electric immer-

sion heaters installed in threaded cou-

plings provided in the side of the basin.

A IP56 enclosure shall house a mag-

netic contactor to energize heaters; a

transformer to provide 24-volt control

circuit power; and a solid-state circuit

board for temperature and low water

cut-off. A control probe shall be located

in the basin to monitor water level

and temperature. The system shall be

capable of maintaining 5°C water tem-

perature at an ambient air temperature

of _____ °C.

Electric Water Level Control:

11.1 Replace this paragraph with the fol-

lowing: The collection basin shall be

heavy-gauge series 300 stainless steel

and shall include the number and type

of suction connections required to

accommodate the out-flow piping sys-

tem shown on the plans. Suction con-

nections shall be equipped with stain-

less steel debris screens. A solid-state

water level control system to monitor

the water level with a multi-relay con-

trol panel pre-wired and mounted in

a IP56 nonmetallic enclosure shall be

provided. The system shall consist of

water level sensing and control units

Unless specified otherwise, a

Metrix switch will be provided.

A double-pole, double-throw

model is also available. If

purchased in conjunction with

the Control System, it is also

factory-wired. The requirement

for manual reset assures that

the cooling tower will be vis-

ited to determine the cause of

excess vibration.

The Marley basin heater components described at left represent our rec-

ommendation for a reliable automatic system for the prevention of basin

freezing. They are normally shipped separately for installation at the job-

site by the installing contractor. When purchased in conjunction with the

enhanced Control System option, however, they are customarily factory-

mounted and tested.

Submerged in basin water,

in which zinc ions are pres-

ent, copper immersion heat-

ers must not be used. Insist

upon stainless steel.

The ambient air temperature

that you insert in the specifi-

cations should be the lowest

1% level of winter tempera-

ture prevalent at site.

Solid-state liquid level controls provide you with state of the art sys-

tems to control and monitor the water level in your cooling tower col-

lection basin. Relays operating in conjunction with suspended stainless

steel electrode probes monitor basin water levels, providing simple

solenoid-valve water makeup or discrete on/off signals to more sophis-

ticated automation controls. Optional configurations might include

makeup along with high and low water level alarm and cutoff, or pump

cutoff. Packaged systems including any of these variations are available.

Consult you Marley sales representative or download a copy of ACC-

NC-9D from spxcooling.com for additional information.