Nc class stainless, Marley, Specifications: options – SPX Cooling Technologies SS-NC-08A User Manual

Page 18: Cooling tower

Advertising
background image

Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Options

18

shall be operated as a stand- alone sys-

tem without the need for a BMS system.

Operator controls shall be mounted

on the front of the enclosure and shall

consist of start and stop control, bypass/

VFD selector switch, Auto/Manual

selector switch, manual speed control,

and solid-state temperature controller.

An emergency bypass selector switch

internal to the panel allowing the cooling

tower fan motor to be run at full speed

shall be furnished. To prevent heating

problems in the cooling tower fan motor

and to assure proper gear box lubrication

the VFD system shall de energize the

motor once 25% motor speed is reached

and cooling is no longer required. The

VFD shall include de-icing logic with auto

canceling and adjustable time. Speed

in De-Ice mode shall not exceed 50 %

motor speed. The cooling tower manu-

facturer shall supply VFD start-up assis-

tance. Tower vibration testing throughout

the speed range is required to identify

and lockout any natural frequency vibra-

tion levels which may exceed CTI guide-

lines.

Miscellaneous Options

Motor out of the Airstream:

6.1

Add the following to the end of this

paragraph: The motor shall be mount-

ed outside the casing of the tower, and

shall be connected to the gear reducer

by a dynamically-balanced, stainless

steel tube and flange driveshaft.

Fan Cylinder Extensions:

9.1 Insert the following after the first

sentence: Fan cylinder extensions

shall be provided to elevate the fan dis-

charge to a height of ___ m above the

fan deck level.

For many years, a feature of

Marley cooling towers was that

the electric motors were located

outside the fan cylinders, where

they were easily accessible, and

where they were not subjected to

the constant humidity that exists

inside the tower plenum.

Although improved motor designs

(insulation, bearings, seals, and

lubricants) have now made it fea-

sible for us to locate the motor inside the tower in close-coupled prox-

imity to the Geareducer

®

(page 7), many users still prefer the motor to

be located outside the humid airstream. If you are among those users—

or are among those who see the wisdom of their thinking—please spec-

ify this option. If you do, however, please require it of all bidders.

Extensions are available in 305mm increments to a maximum height

equal to the diameter of the fan. Such extensions may be considered

necessary in order to elevate the discharge beyond the bounds of an

enclosure. Discuss applicability with your local Marley sales representa-

tive.