Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Options

22

______ psf, as well as a ______ seismic

load. The fan deck and hot water basin

covers shall be designed for 50 psf live

load or a 200 lb. concentrated load.

Guardrails, where specified, shall be

capable of withstanding a 200 lb. con-

centrated live load in any direction, and

shall be designed in accordance with

OSHA guidelines.

Multicell Basin Equalizer Outlets:

11.1 Add the following paragraph in the

Access section: A hole and bolt circle

shall be provided in the depressed sec-

tion of the basin for equalizer piping

between cells. A full-face, .25" thick, 50

durometer gasket shall be provided at

each equalizer location.

Basin Sweeper Piping:

11.1 Add the following paragraph in the

Access section: The cold water basin

shall be equipped with PVC sweeper

piping with plastic eductor nozzles.

The piping should create a grid under

the fill and force all dirt and debris to

the depressed section of the collection

basin.

Extended Geareducer Lube Line

with Dipstick:

6.1

Add the following paragraph in the

Mechanical Equipment section: An

external oil level dipstick shall be locat-

ed adjacent to the motor at the fan

deck surface and shall be accessible

from a portable maintenance ladder.

■

Used as water level equalizers between multicell towers. Not intended

for water migration. Piping and attachment hardware by others. Flat

faced flange required.

■

PVC sweeper piping and Lakos nozzles. Designed for the following

flows at 20 psig:

NC8301 thru NC8304, 33m

3

/h

NC8305, 47m

3

/h

NC8306 thru NC8312, 64m

3

/h

■

The dipstick option is accessible from a portable maintenance ladder

on one and two cell towers only. Maintenance considerations recom-

mends this option be combined with the ladder and guardrail option on

installations of three or more cells since the dipstick cannot be reached

without accessing the fan deck.