Specifications

Specification Value

Marley

/

NC Class Stainless

Cooling Tower

/

Specifications: Base

6

designed for 2.4kPa live load or a 91kg

concentrated load. Guardrails, where

specified, shall be capable of with-

standing a 890N concentrated live load

in any direction, and shall be designed

in accordance with OSHA guidelines.

5.0

Construction:

5.1

Except where otherwise specified, all

components of the cooling tower shall

be fabricated of heavy-gauge, series

300 stainless steel. The tower shall be

capable of withstanding water having a

chloride content (NaCl) up to 750 mg/L;

a sulfate content (SO4) up to 1200

mg/L; a calcium content (CaCO3) up to

800 ppm; silica (SiO2) up to 150 mg/L;

and design hot water temperatures

up to 52°C. The circulating water shall

contain no oil, grease, fatty acids, or

organic solvents.

5.2

The specifications, as written, are

intended to indicate those materials

that will be capable of withstanding

the above water quality in continuing

service, as well as the loads described

in paragraph 4.1. They are to be regard-

ed as minimum requirements. Where

component materials peculiar to indi-

vidual tower designs are not specified,

the manufacturers shall take the above

water quality and load carrying capabili-

ties into account in the selection of

their materials of manufacture.

shipped, handled, hoisted—and ultimately operated in a normal cooling

tower environment. Most NC Class models will withstand significantly

higher wind and seismic loads. If your geographic location dictates

higher wind load or seismic load values, please make the appropriate

changes, after discussion with your Marley sales representative.

Note: Some countries and states (Florida) require structure not anchor-

age. Check with you local officials.

1.44k/Pa windload, .3g seismic load—applicable for most applications

but consult the local code official for actual requirements.

2.4kPa live load, 890N concentrated load—ensures the tower can be

safely accessed for routine maintenance when a guardrail is installed as

well ensuring the end user complies with government safety laws.

For pure resistance to corrosion—coupled with the capability to meet

stringent fire and building codes—there is no substitute for stainless

steel! No paints or electrostatically-applied coatings, however exotic

they may be, can match stainless steel's ability to withstand adverse

operating conditions.

Although SPX Cooling Technologies makes use of many structural FRP

components in various other product lines, they are held to a relative

minimum in the NC Class Stainless line. This is to assure that there will

be no question as to the structural integrity, fire resistance, and life

expectancy in the mind of the owner.

Except for those unusual operating situations where the circulating

water may be so laden with suspended solids, algae, fatty acids, prod-

uct fibers, active organisms reflected in BOD, and the like that plug-

ging of film type fill is a probability, the NC Class Stainless is relatively

immune to poor water quality. Where such conditions do exist, how-

ever, thought should be given to the prevention of such carryover—or

to the use of a Marley splash-fill product. Please discuss your situation

with your Marley sales representative.