Siemens SCALANCE X-200 User Manual

Page 13

Advertising
background image

Network Topologies

3.1 Network Topologies

Ring Topology

Figure 3-4

Ring Topology, Example with SCALANCE X204-2 and SCALANCE X-400 as

Redundancy Manager

To increase availability, optical or electrical bus topologies made up of SCALANCE X-200

switches with a SCALANCE X414-3E, OSM version 2, or ESM version 2 configured as a

redundancy manager can be closed to form a ring. The SCALANCE X-200 switches are first

connected over their ring ports to form a bus. The two ends of the bus are closed to form a

ring by a SCALANCE X414-3E or OSM / ESM operating in the redundancy manager mode.

In contrast to the ring ports of the SCALANCE X-200 switches, the ring ports of the

redundancy manager are disconnected from each other during problem-free network

operation.
The SCALANCE X414-3E or OSM / ESM operating in the redundancy manager mode

monitors the connected bus over its ring ports and switches the ring ports through if there is

an interruption on the connected bus; in other words, it restores a functioning bus over this

substitute path. Reconfiguration takes place within 0.3 s.
As soon as the problem has been eliminated, the original topology is restored; in other

words, the ring ports in the redundancy manager are once again disconnected from each

other.

Industrial Ethernet SCALANCE X-100 and SCALANCE X-200 Product Line
Commissioning Manual, 1,

3-3

Advertising
This manual is related to the following products: