Datanet hub specifications – Siemens DataNET Hub (DNH) User Manual

Page 17

Advertising
background image

2000585-001

Introduction

•••• 9

DataNET Hub Specifications,

Continued

The Table below compares key communication features between using
Advance Data Hiway, Ethernet, or DataNET.

Feature Advance

Data

Hiway Ethernet

DataNET

Speed

14.2 KB/Sec

10 M baud

2. 048 M baud

Redundant Yes

No

Yes

Number of Units in
Maxum System

248 1200 1200

The following Table should be used when evaluating or selecting cable
for an existing or new DataNET installation.

Cable Type

Vendors & P/N

Installation Notes

Fiber Optic

MM 62.5/125; 2 Fiber Conductors

SAA P/N 1270002-002

Industry Available from Mul-
tiple Vendors

New Installation as an al-
ternative to copper cable

Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)

2- Conductor Copper Wire

SAA P/N 1686002-001

Belden P/N 9182

for

Belden Armored Cable or-

der

SAA P/N 1680000-002

Recommended for Single
Channel

Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)

4-Conductor Copper Wire

SAA P/N 1681000-003

Belden P/N SSD1743

Recommended for Dual
Channel

Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)

Ethernet Cat 5 Unshielded Twisted
pair (UTP)

SAA P/N 1681003-006

Industry Available from Mul-
tiple Vendors

Recommended for short
distances or within shelters.

Max distance from analyzer
to hub or between hubs 600
meters (2000 ft)

Communication
Comparisons

DataNET Cable