Ce installations – Siemens DataNET Hub (DNH) User Manual

Page 32

Advertising
background image

24

•••• Installation

2000585-001

CE Installations,

Continued

3. A split ferrite filter must be clamped to DataNET copper wire and

fixed immediately to the outside of the DNH; use Siemens Applied
Automation part number 1173000-013 ferrite contained in the CE In-
stallation Kit. This is required to meet the Conducted Immunity re-
quirement for CE/EMC Heavy Industrial. All other CE/EMC Heavy
Industrial requirements are met without the use of a ferrite clamp.

4. Shielded Ethernet cable must be used for all Ethernet connections,

in and outside the GC, and coupled through the enclosure using a
shielded RJ-45 coupler; use Siemens Applied Automation part num-
ber 1183200-003 contained in the CE Installation Kit. A mounting
plate (Siemens Applied Automation part number 2020261-001) is
also available to accomplish this. If needed for Zone 1 installation,
Siemens Applied Automation part numbers 2017984-001 and
2017985-001 are available to maintain purge. If a PG gland is used
to make the 360-degree termination of the Ethernet shield at the en-
closure, the Installation Kit and other parts are not required.

Advertising