1-7. Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 1-13 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4" (ш6.35)

0.279

ш3/8" (ш9.52)

0.602

Required amount of charge = (Amount of refrigerant

charge per meter of each size of liquid tube

× its tube

length) + (...) + (...)

*Always charge accurately using a scale for weighing.

Table 1-12 Required Copper Tubing Dimensions

Unit: in. (mm)

Table 1-14 Refrigerant Charge Amount at Shipment (for outdoor unit)

1-8. System Limitations

Table 1-15 System Limitations

Number of max. connectable indoor units

Outdoor units (Type)

CHX03652

6

CHX06052

9

Max. allowable indoor/outdoor capacity ratio

50 – 130%

Heat pump unit

(Single-phase)

(oz)

CHX03652

123

CHX06052

123

Gas tubing size (in. (mm))

90

° elbow

45

° elbow

U-shape tube bend (R2-3/8" – 4" (60 – 100))

Trap bend

1/2" (12.7)

1

0.8

3

7.5

5/8" (15.88)

1.1

0.9

3.4

9.2

3/4" (19.05)

1.4

1

4.1

10.5

Y-branch distribution joint

Equivalent length conversion not needed.

Ball valve for service

Equivalent length conversion not needed.

1-6. Straight Equivalent Length of Joints

Design the tubing system by referring to the following table for the straight equivalent length of joints.

Table 1-11 Straight Equivalent Length of Joints

Unit: ft.

Material

O

Copper tube

Outer diameter

1/4 (6.35)

3/8 (9.52)

1/2 (12.7)

5/8 (15.88)

3/4 (19.05)

Wall thickness

1/32 (0.8)

1/32 (0.8)

1/32 (0.8)

5/128 (1.0)

over 5/128 (1.0)