Sanyo AHX0952 User Manual

Page 45

Advertising
background image

45

D

Fig. 3-79

Hole-in-anchor
Hole-in-plug

Concrete

Insert

Suspension bolt (M10 or 3/8")
(field supply)

3-20. Suspending the Indoor Unit

Depending on the ceiling type:

Insert suspension bolts as shown in Fig. 3-79

or

Use existing ceiling supports or construct a suitable support as
shown in Fig. 3-80.

Fig. 3-80

Fig. 3-81

Ceiling tiles

Ceiling support

Suspension bolt

25/

3

2

"

– 1-

3

1/

3

2

"

Hexagonal nuts
and washers
(2 sets)

WARNING

It is important that you use extreme care
in supporting the indoor unit inside the
ceiling. Ensure that the ceiling is strong
enough to suport the weight of the unit.
Before hanging the unit, test the strength
of each attached suspension bolt.

(1) When placing the unit inside the ceiling, determine the pitch

of the suspension bolts referring to the dimensional data given
previously. (Figs. 3-77 and 3-78)

Tubing must be laid and connected inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay
the tubing into position for connection to the unit before placing
the unit inside the ceiling.

(2) Screw in the suspension bolts allowing them to protrude from

the ceiling as shown in Fig. 3-79. (Cut the ceiling material, if
necessary.)

(3) Suspend and fix the indoor unit using the 2 hexagonal nuts

(field supply) and special washers (supplied with the unit) as
shown in Fig. 3-81.

Air-outlet grille

Air-intake grille

Fig. 3-82

07-056 Mini_ECOi_II_NA 3/19/07 2:41 PM Page 45